Technische Daten iTEMP TMT162
50 Endress+Hauser
communication lines (fieldbus systems) and power supply is diverted to ground. The
functionality of the transmitter is not affected as no problematic voltage drop occurs.
Connection data:
Maximum continuous voltage (rated voltage) U
C
= 42 V
DC
Nominal current I = 0.5 A
at T
amb.
= 80 °C (176 °F)
Surge current resistance
Lightning surge current D1 (10/350 µs)
Nominal discharge current C1/C2 (8/20 µs)
I
imp
= 1 kA (per wire)
I
n
= 5 kA (per wire)
I
n
= 10 kA (total)
Temperature range –40 to +80 °C (–40 to +176 °F)
Series resistance per wire 1.8 Ω, tolerance ±5 %
4
+
-
1
2
3
5
6
+
-
3
4
S1
3
S2
-
+
+
-
!
+
Sensor 2
Sensor 1
-
Bus connection and
supply voltage
A0033027-EN
 16 Electrical connection of surge arrester
Grounding
The device must be connected to the potential equalization. The connection between the
housing and the local ground must have a minimum cross-section of 4 mm
2
(13
AWG) .
All ground connections must be secured tightly.
13.4 Performance characteristics
Response time The measured value update depends on the type of sensor and connection method and
moves within the following ranges:
Resistance thermometer (RTD) 0.9 to 1.3 s (depends on the connection method 2/3/4-wire)
Thermocouples (TC) 0.8 s
Reference temperature 0.9 s
When recording step responses, it must be taken into account that the times for the
measurement of the second channel and the internal reference measuring point are
added to the specified times where applicable.
Reference operating
conditions
Calibration temperature: +25 °C
±3 K (77 °F ±5.4 °F)
Supply voltage: 24 V DC
4-wire circuit for resistance adjustment