iTEMP TMT162 Technische Daten
Endress+Hauser 57
Long-term drift, thermocouples (TC) and voltage transmitters
Designation Standard Long-term drift (±)
1)
after 1 year after 3 years after 5 years
Based on measured value
Type A (30)
IEC 60584-1
≤ 0.048% * (MV - LRV) or
0.46 °C (0.83 °F)
≤ 0.072% * (MV - LRV) or
0.69 °C (1.24 °F)
≤ 0.1% * (MV - LRV) or
0.94 °C (1.69 °F)
Type B (31) 1.08 °C (1.94 °F) 1.63 °C (2.93 °F) 2.23 °C (4.01 °F)
Type C (32)
IEC 60584-1 / ASTM
E988-96
≤ 0.038% * (MV - LRV) or
0.41 °C (0.74 °F)
≤ 0.057% * (MV - LRV) or
0.62 °C (1.12 °F)
≤ 0.078% * (MV - LRV) or
0.85 °C (1.53 °F)
Type D (33) ASTM E988-96
≤ 0.035% * (MV - LRV) or
0.57 °C (1.03 °F)
≤ 0.052% * (MV - LRV) or
0.86 °C (1.55 °F)
≤ 0.071% * (MV - LRV) or
1.17 °C (2.11 °F)
Type E (34)
IEC 60584-1
≤ 0.024% * (MV - LRV) or
0.15 °C (0.27 °F)
≤ 0.037% * (MV - LRV) or
0.23 °C (0.41 °F)
≤ 0.05% * (MV - LRV) or
0.31 °C (0.56 °F)
Type J (35)
≤ 0.025% * (MV - LRV) or
0.17 °C (0.31 °F)
≤ 0.037% * (MV - LRV) or
0.25 °C (0.45 °F)
≤ 0.051% * (MV - LRV) or
0.34 °C (0.61 °F)
Type K (36)
≤ 0.027% * (MV - LRV) or
0.23 °C (0.41 °F)
≤ 0.041% * (MV - LRV) or
0.35 °C (0.63 °F)
≤ 0.056% * (MV - LRV) or
0.48 °C (0.86 °F)
Type N (37) 0.36 °C (0.65 °F) 0.55 °C (0.99 °F) 0.75 °C (1.35 °F)
Type R (38) 0.83 °C (1.49 °F) 1.26 °C (2.27 °F) 1.72 °C (3.10 °F)
Type S (39) 0.84 °C (1.51 °F) 1.27 °C (2.29 °F) 2.23 °C (4.01 °F)
Type T (40) 0.25 °C (0.45 °F) 0.37 °C (0.67 °F) 0.51 °C (0.92 °F)
Type L (41)
DIN 43710
0.20 °C (0.36 °F) 0.31 °C (0.56 °F) 0.42 °C (0.76 °F)
Type U (42) 0.24 °C (0.43 °F) 0.37 °C (0.67 °F) 0.50 °C (0.90 °F)
Type L (43) GOST R8.8585-2001 0.22 °C (0.40 °F) 0.33 °C (0.59 °F) 0.45 °C (0.81 °F)
Voltage transmitter (mV)
–20 to 100 mV ≤ 0.027% * (MV - LRV) or 5.5 µV ≤ 0.041% * (MV - LRV) or 8.2 µV
≤ 0.056% * (MV - LRV) or
11.2 µV
1) Whichever is greater
Long-term drift analog output
Long-term drift D/A
1)
(±)
after 1 year after 3 years after 5 years
0.021% 0.029% 0.031%
1) Percentages based on the configured span of the analog output signal
Influence of reference
junction
Pt100 DIN IEC 60751 Cl. B (internal reference junction with thermocouples TC)
13.5 Environment
Ambient temperature
range
Without display: –40 to +85
°C (–40 to +185 °F)
With display and/or surge arrester module: –40 to +80 °C (–40 to +176 °F)
SIL mode: –40 to +75 °C (–40 to +167 °F)