iTEMP TMT162 Operating menu and parameter description
Endress+Hauser 81
Description Indicates whether the device has been ordered with SIL certification.
The SIL option is required to operate the device in the SIL mode.
User entry No
Yes
Factory setting No
Operational state
Navigation Setup → Advanced setup → SIL → Operational state
Description Displays the device operational state in the SIL mode.
Display Checking SIL option
Startup normal mode
Wait for checksum
Self diagnostic
Normal mode
Download active
SIL mode active
Safe para start
Safe param running
Save parameter values
Parameter check
Reboot pending
Reset checksum
Safe state - Active
Download verification
Upload active
Safe state - Passive
Safe state - Panic
Safe state - Temporary
Factory setting Normal mode
Enter SIL checksum
Navigation Setup → Advanced setup → SIL → Enter SIL checksum
Description If the value '0' is entered in the SIL checksum, the device switches from the SIL mode to the
normal mode. Users can also quit the SIL mode using the Deactivate SIL parameter.
User entry 0 to 65535
Factory setting 0