PROline Prosonic Flow 93 FOUNDATION Fieldbus 3 Transducer Blocks (transmission blocks)
Endress+Hauser 131
Configuration -
Xline
Calculated
AUTO - OOS Use this parameter to indicate which “calculated main value” from
the measured values of both channels is displayed.
"CALC. VOLUME FLOW” must be selected in one of the following
parameters so that the value appears in the line desired:
•“Main Line - Assign” parameter for display in the main line
•“Add. Line - Assign” parameter for display in the additional line
•“Info Line - Assign” parameter for display in the information line
Note!
This parameter is not active if "OFF" was selected on one channel in
the “Sensor Param. - Measurement” parameter, (see Page 122).
Options:
(CH1 + CH2) / 2
CH1 + CH2
CH1 - CH2
Factory setting:
(CH1 + CH2) / 2
Operation -
Test Display
AUTO - OOS Use this parameter to test the operability of the local display and its
pixels.
Options:
OFF
ON
Factory setting:
OFF
Test sequence:
1. Start the test by selecting ON.
2. All pixels of the main line, additional line and information line are
darkened for minimum 0.75 seconds.
3. Main line, additional line and information line show an “8” in each
field for minimum 0.75 seconds.
4. Main line, additional line and information line show a “0” in each
field for minimum 0.75 seconds.
5. Main line, additional line and information line show nothing (blank
display) for minimum 0.75 seconds.
When the test is completed, the display returns to its initial state.
Parameter
→ OFF.
“TRANSDUCER_DISP” (E+H parameters) / base index 1500
Parameter Write access
with operating
mode
(MODE_BLK)
Description