Mounting procedure Proline Prosonic Flow W 400 HART
36 Endress+Hauser
3. Position the sensor housing on the sensor holder.
A0043377
24 Positioning the sensor housing
4. Attach the sensor housing to the sensor holder by locking the bracket into place.
A0043378
25 Fastening the sensor housing
5. Connect the sensor cable to the adapter cable.
This completes the mounting procedure. The sensors can be connected to the
transmitter via the connecting cables.
• To ensure good acoustic contact, the visible measuring pipe surface must be clean
and free from flaking paint and/or rust.
• If necessary, the holder and sensor housing can be secured with a screw/nut or a
lead seal (not supplied).
• The bracket can only be released using an auxiliary tool e.g. screwdriver).
Installing sensors – medium/large nominal diameters DN 50 to 4000 (2 to 160")
Installation for measurement via 1 traverse
Requirements
• The installation distance and wire length are known
• Strapping bands are pre-assembled.