Commissioning Proline Prowirl R 200 HART
108 Endress+Hauser
Parameter Prerequisite Description Selection / User
entry
Factory setting
Mol% n-C4H10 The following conditions are
met:
In the Select medium
parameter, the Gas option is
selected.
In the Select gas type
parameter, the Gas
mixture option is selected
and in the Gas mixture
parameter, the Butane
C4H10 option is selected.
Or
In the Select gas type
parameter, the Natural
gas option is selected and
in the Density
calculation parameter,
the ISO 12213- 2 option
is selected.
Or
In the Select medium
parameter, the Liquid
option is selected and in the
Select liquid type
parameter, the LPG option is
selected.
Enter amount of substance for
the gas mixture.
0 to 100 % 0 %
Mol% n-C5H12 The following conditions are
met:
In the Select medium
parameter, the Gas option is
selected.
In the Select gas type
parameter, the Natural gas
option is selected.
In the Density calculation
parameter, the ISO 12213-
2 option is selected.
Enter amount of substance for
the gas mixture.
0 to 100 % 0 %
Mol% n-C6H14 The following conditions are
met:
In the Select medium
parameter, the Gas option is
selected.
In the Select gas type
parameter, the Natural gas
option is selected.
In the Density calculation
parameter, the ISO 12213-
2 option is selected.
Enter amount of substance for
the gas mixture.
0 to 100 % 0 %
Mol% n-C7H16 The following conditions are
met:
In the Select medium
parameter, the Gas option is
selected.
In the Select gas type
parameter, the Natural gas
option is selected.
In the Density calculation
parameter, the ISO 12213-
2 option is selected.
Enter amount of substance for
the gas mixture.
0 to 100 % 0 %