Technical data Proline Prowirl R 200 HART
174 Endress+Hauser
Calculated measured variables
Order code for "Sensor version; DSC sensor; measuring tube"
Option Description Measured variable
AA Volume; 316L; 316L Under constant process conditions:
Mass flow
1)
Corrected volume flow
The totalized values for:
Volume flow
Mass flow
Corrected volume flow
AB Volume; Alloy C22; 316L
BA Volume high-temperature; 316L; 316L
BB Volume high-temperature; Alloy C22; 316L
1) A fixed density must be entered for calculating the mass flow (Setup menu → Advanced setup submenu →
External compensation submenu → Fixed density parameter).
Order code for "Sensor version; DSC sensor; measuring tube"
Option Description Measured variable
CA Mass; 316L; 316L (integrated temperature measurement) Corrected volume flow
Mass flow
Calculated saturated steam pressure
Energy flow
Heat flow difference
Specific volume
Degrees of superheat
CB Mass; Alloy C22; 316L (integrated temperature
measurement)
DA Mass steam; 316L; 316L (integrated pressure/temperature
measurement)
DB Mass gas/liquid; 316L; 316L (integrated pressure/
temperature measurement)
Measuring range The measuring range is dependent on the nominal diameter, the fluid and environmental
influences.
The following specified values are the largest possible flow measuring ranges (Q
min
to
Q
max
) for each nominal diameter. Depending on the fluid properties and
environmental influences, the measuring range may be subject to additional
restrictions. Additional restrictions apply to both the lower range value and the upper
range value.
Flow measuring ranges in SI units
DN
[mm]
Liquids
[m³/h]
Gas/steam
[m³/h]
25R, 40S 0.1 to 4.9 0.52 to 25
40R, 50S 0.32 to 15 1.6 to 130
50R, 80S 0.78 to 37 3.9 to 310
80R, 100S 1.3 to 62 6.5 to 820
100R, 150S 2.9 to 140 15 to 1 800
150R, 200S 5.1 to 240 25 to 3 200
200R, 250 S 11 to 540 57 to 7 300
Flow measuring ranges in US units
DN Liquids Gas/steam
[in] [ft³/min] [ft³/min]
1R, 1½S 0.061 to 2.9 0.31 to 15
1½R, 2S 0.19 to 8.8 0.93 to 74
2R, 3S 0.46 to 22 2.3 to 180