Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry
Factory setting
Switch output function The Switch option is selected
in the Operating mode
parameter.
Select function for switch
output.
• Off
• On
• Diagnostic
behavior
• Limit
• Status
Off
Assign diagnostic behavior • In the Operating mode
parameter, the Switch
option is selected.
• In the Switch output
function parameter, the
Diagnostic behavior option
is selected.
Select diagnostic behavior for
switch output.
• Alarm
• Alarm or warning
• Warning
Alarm
Assign limit • The Switch option is
selected in the Operating
mode parameter parameter.
• The Limit option is selected
in the Switch output
function parameter
parameter.
Select process variable for limit
function.
• Volume flow
• Corrected volume
flow
• Mass flow
• Flow velocity
• Temperature
• Pressure
• Calculated
saturated steam
pressure
*
• Total mass flow
*
• Energy flow
*
• Heat flow
difference
*
• Reynolds number
*
• Totalizer 1
• Totalizer 2
• Totalizer 3
Volume flow
Assign flow direction check • The Switch option is
selected in the Operating
mode parameter.
• The Flow direction check
option is selected in the
Switch output function
parameter.
Select process variable for flow
direction monitoring.
• Off
• Volume flow
• Mass flow
• Corrected volume
flow
Volume flow
Assign status • The Switch option is
selected in the Operating
mode parameter.
• The Status option is
selected in the Switch
output function parameter.
Select device status for switch
output.
Low flow cut off Low flow cut off
Switch-on value • In the Operating mode
parameter, the Switch
option is selected.
• In the Switch output
function parameter, the
Limit option is selected.
Enter measured value for the
switch-on point.
Signed floating-point
number
Country-specific:
• 0 m³/h
• 0 ft³/h
Switch-off value • In the Operating mode
parameter, the Switch
option is selected.
• In the Switch output
function parameter, the
Limit option is selected.
Enter measured value for the
switch-off point.
Signed floating-point
number
Country-specific:
• 0 m³/h
• 0 ft³/h