EasyManuals Logo

FCI ST100A Series User Manual

FCI ST100A Series
170 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #38 background imageLoading...
Page #38 background image
INSTALLATION ST100A Series Flow Meter
30 Fluid Components International LLC
Modbus Configuration
Refer to Figure 25 on page 29. To set J8 for Modbus operation install a 2 mm jumper shunt onto the J12 and J13 jumper pins as shown in
Table 3 below.
Table 3 – Modbus Select Jumpers
J12
J13
Install Jumper Shunt over Pins
1 and 2
1 and 2
Note: 1. = Jumper Installed
Use the 2 mm line configuration jumpers J9, J10, and J11 as needed for your specific application.
Termination (End of Line) is typically required for applications with faster data rates or long cable lengths or both. Enable the
instrument’s terminator as required for your application.
Line biasing is used to ensure that lines are at a known state (noise can cause a false trigger on a floating line). Check first that the
RS-485 network is not already biased before enabling line biasing. Only use one of these jumpers, J9 or J11, not both.
Table 4 below summarizes the line configuration jumper functions.
Table 4 – Modbus Line Configuration Jumpers
J9
J10
J11
Line Biasing (pullup)
150 Ω Termination
Line Biasing (pulldown)
F
OUNDATION Fieldbus/PROFIBUS Connections (Option)
Referencing Figure 25 on page 29, connect the F
OUNDATION Fieldbus/PROFIBUS device/network to Phoenix connector J8 on the main
board (not to be confused with the auxiliary board J8 connector that provides the 3
rd
4-20 mA output). Note that the FF/PROFIBUS
connector is also used for the Modbus wiring (only one interface can be active at a time). Connector J8 accepts 2412 AWG (0.2 mm
2
1.5 mm
2
) wire (refer to Table 2, page 21 for wire size vs. length info). It is recommended that wiring have a flammability rating of UL 2556
VW-1 or equivalent.
Connect the ST100A Series to a Fieldbus/PROFIBUS device/network as shown in Figure 27 below. Note that devices are connected in
parallel (star fashion).Use a terminator as appropriate for your application. For details on PROFIBUS operation refer to the ST100A Series
PROFIBUS PA manual 06EN003483. For details on F
OUNDATION Fieldbus operation refer to the ST100A Series FOUNDATION Fieldbus
manual 06EN003482.
Note:
Foundation Fieldbus/PROFIBUS operation is provided through an optional add-on card that plugs into the ST100A
Series main board.
Figure 27Fieldbus/PROFIBUS Wiring
ST100A
Fieldbus/
PROFIBUS
Interface (J8)
Field
Device
Add’l
Field
Device
Wire Pair
FB_A
FB_B
Terminator Terminator
Signals
T
T
C01416-1-1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the FCI ST100A Series and is the answer not in the manual?

FCI ST100A Series Specifications

General IconGeneral
BrandFCI
ModelST100A Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals