EasyManua.ls Logo

FCI ST100A Series - Maintenance; General Maintenance; Calibration

FCI ST100A Series
170 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ST100A Series Flow Meter OPERATION
Fluid Components International LLC 81
Checking the Totalizer 2 (Upper Count/Rollover Count) Value
Referring to Checking the Totalizer 1 (Lower Count) Value above,
repeat step 1, but specify register #4113 instead (Length =2).
Repeat step 2 above (skip if already connected and configured).
See the figure below for a “Rollover count” number example.
Checking/Setting the Totalizer Max. Value
Referring to Checking the Totalizer 1 (Lower Count) Value above, repeat
step 1, but specify register #4115 instead (Length =2).
Repeat step 2 above (skip if already connected and configured).
See the figure below for a “Ceiling value” number example.
Resetting the Totalizer Value
Referring to Checking the Totalizer 1 (Lower Count) Value above,
repeat step 1, but specify register #4117 instead (Length = 1).
Repeat step 2 above (skip if already connected and configured).
Double click on the register number (see pointer in the figure below).
A pop-up Write Register dialog displays. Enter the defined hex value,
0xABCD, in the window’s value field, and then click Update.
Starting/Stopping the Totalizer Count
Referring to Checking the Totalizer 1 (Lower Count) Value above,
repeat step 1, but specify register #4118 instead (Length = 1).
Repeat step 2 above (skip if already connected and configured).
Double click on the register number (see pointer in the figure below).
A pop-up Write Register window displays. Enter the defined value (1 =
start or 0 = stop) in the window’s value field, and then click Update.

Table of Contents

Related product manuals