EasyManua.ls Logo

Fimer PVS980-58 - Page 105

Fimer PVS980-58
160 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data 103
Short-circuit withstand
strength (IEC 60439-1)
Maximum allowable prospective short-circuit current:
50 kA or 65 kA (only with F296 in the 600 V model).
When you use temporary grounding (connect two sets of grounding cables to
the connecting knobs of the AC and DC busbars and PE of the inverter): The
maximum permitted prospective short-circuit current decreases to 45 kA /
1 s. To maintain the 65 kA rating, the fault current duration must be limited to
0.5 s. If the connected grounding cables and clamps are not equivalent to the
prospective short-circuit rating of the inverter, the total rating will be lower.
Frequency 45 to 65 Hz withstand with nominal dimensioning (grid-compliance may
require disconnection at stricter values).
Imbalance The inverter does not cause imbalance.
Voltage dips Max. 0% Refer to the Firmware manual.
Fundamental power factor
(cos phi
1
)
1
Power factor (cos phi
1
)
adjustment range
0…1 capacitive or inductive
The graph illustrates inverter operation at the nominal AC voltage and
nominal ambient (50 °C) temperature. At 35 °C, up to 110% power available.
Refer to Ratings on page 94.
Current Refer to Ratings on page 94.
Maximum output fault
current
(Tested by making direct 3-
phase short circuit to
inverter output when
inverter is feeding nominal
current)
Output mains:
Peak: 5600 A
3 cycles (average): 370 A
Duration: 25 ms
3-phase customer aux:
Peak: 5000 A
3 cycles (average): 310 A
Duration: 1 ms
1-phase 115 V service outlet:
Peak: 400 A
3 cycles (average): 60 A
Duration: 3 ms
1-phase 230 V service outlet:
Peak: 470 A
3 cycles: (average) 100 A
Duration: 7 ms
P (%)
Q (%)
90
80
70
60
50
40
30
20
10
-10
-20
-30
-40
-50
-60
-70
-80
10 20 30 40 50 60 70 80 90 1000
100
-90
-100
Q (%) Available reactive power as a percentage of the
nominal apparent power
P (%) Available active power as a percentage of the
nominal apparent power
100
2
- P(%)
2
Q
max
(%) =
110
110
-110
35 °C
50 °C

Table of Contents

Related product manuals