Technical data 105
Auxiliary power connection data
Standard delivery
Voltage 230 V AC (default)
115 V AC (option +G397)
Frequency 50/60 Hz
Service outlet 10 A residual current circuit breaker (30 mA/A-type) for the socket outlet.
Allowed electrical system TN-S (grounded) system. For IT (ungrounded) systems, contact FIMER for
instructions.
Overvoltage category
(IEC 62109-1, IEC 60664-1)
2
1-phase output (with option +G410)
Voltage 230 V AC (default)
115 V AC (option +G397)
100 V AC (option +G396)
Power 2 kVA
Frequency 50/60 Hz
Protection The current rating depends on the voltage level:
10 A for 230 V AC (default)
20 A for 115 V AC (option +G397)
25 A for 100 V AC (option +G396)
Service outlet A 2-pole miniature circuit breaker (K- or D-curve) for the output on a terminal
strip 0X13 for external devices (+G410).
Max. conductor size (0X13) 6 mm
2
/10 AWG
Allowed electrical system TN-S (grounded) system. For IT (ungrounded) systems, contact FIMER for
instructions.
Overvoltage category
(IEC 62109-1, IEC 60664-1)
2
3-phase fused output from the mains
Voltage 600/630/660/690 V AC depending on the voltage class of the inverter
Maximum current IEC 32 A / UL 30 A (option +G429)
IEC 63 A / UL 60 A (option +G430)
Frequency 50/60 Hz