106 Technical data
Protection IEC:
32 A gG type fuses (option +G429)
63 A gG type fuses (option +G430)
UL (option +C129):
30 A J type fuses (option +G429)
60 A J type fuses (option +G430)
When option +G429/+G430 is selected, make sure that the maximum current
peak values and durations are not exceeded, for example, when the output is
used to supply the external transformer.
When option +G429/+G430 is selected, the maximum available output
power available depends on the grid voltage and the temperature inside the
inverter, which is about 20 °C higher than the ambient temperature. Consider
the maximum power values in the tables below when you design the load for
the output.
Max. conductor size (0X12)
50 mm
2
/AWG 1/0
Allowed electrical system IT (ungrounded) system
Overvoltage category
(IEC 62109, IEC 60664-1)
3
Maximum current peak:
t [s] I [A] (+G429) I [A] (+G430)
0.01 160 400
0.1 120 290
1 90 220
10 70 160
Maximum power:
T [°C]
ambient
S [kV AC] (+G429)
600 630 660 690
30 30 31 33 34
40 28 29 31 32
50 26 28 29 30
60 25 26 27 29
70 23 25 26 28
Maximum power:
T [°C]
ambient
S [kV AC] (+G430)
600 630 660 690
30 59 62 65 68
40 56 59 62 64
50 53 56 58 61
60 50 52 55 57
70 47 49 51 54