112 Technical data
Materials
Cabinet Outer plates:
EN 1.4301/2B (ASTM 304) steel sheet (thickness 1.5 mm [0.06 n.])
AlMg3 aluminum sheet (thickness 2 mm [0.08 in]) with PE powder coating
(thickness approximately 80 micrometers), color: RAL 7035
Frame: EN 1.4301/2B (ASTM 304) steel
Assembly and side plates inside the cabinet: Hot-dip zinc-coated steel sheet
Air grilles Frame: EN 1.4301/2B (ASTM 304) steel with PE powder coating (thickness
approximately 80 micrometers), color: RAL 7035
Grille profile: AlMgSi AW-6060/6063 T5 with anodizing AA10, clear
Busbars Tin-plated metal
Fire safety of materials
(IEC 60332-1)
Insulating materials and non-metallic items: flame retardant
Package Frame: Wood or plywood
Plastic wrapping: Low-density polyethylene (LDPE)
Bands: Polypropylene (PP) or steel
Disposal The inverter contains raw materials that should be recycled to preserve
energy and natural resources. The package materials are environmentally
compatible and recyclable. All metal parts can be recycled. The plastic parts
can either be recycled or burned under controlled circumstances, according
to local regulations. Most recyclable parts are marked with recycling marks.
If recycling is not feasible, all parts excluding electrolytic capacitors and
printed circuit boards can be disposed of in landfills. The printed circuit
boards may contain lead which is classified as hazardous waste within the
EU. They must be removed and handled according to local regulations.
For further information on environmental matters and recycling, contact your
local FIMER representative.
Coolant medium in heat
exchangers
R134a (1,1,1,2-tetrafluoroethane)
The coolant is a non-flammable gas that is commonly used as a refrigerant in
domestic and industrial applications.The coolant is in hermetically sealed
containers which do not need to be opened. When the inverter is disposed of
or the cooling element is replaced, the cooling elements must be recycled
and handled according to local regulations.
For further information on environmental matters and recycling, contact your
local FIMER representative.