108 Technical data
Efficiency
The inverter complies with efficiency standards IEC 61683 and EN 50530.
Maximum efficiency without auxiliary power
DC voltage 850 V 975 V 1100 V
PVS980-58-1818kVA-I 98.82% 98.51% 98.40%
DC voltage 893 V 997 V 1100 V
PVS980-58-1909kVA-J 98.81% 98.55% 98.47%
DC voltage 935 V 1018 V 1100 V
PVS980-58-2000kVA-K 98.82% 98.58% 98.51%
DC voltage 978 V 1039 V 1100 V
PVS980-58-2091kVA-L 98.85% 98.69% 98.58%
Maximum efficiency with auxiliary power
DC voltage 850 V 975 V 1100 V
PVS980-58-1818kVA-I 98.65% 98.40% 98.26%
DC voltage 893 V 997 V 1100 V
PVS980-58-1909kVA-J 98.65% 98.38% 98.33%
DC voltage 935 V 1018 V 1100 V
PVS980-58-2000kVA-K 98.70% 98.45% 98.40%
DC voltage 978 V 1039 V 1100 V
PVS980-58-2091kVA-L 98.70% 98.58% 98.44%
European efficiency without auxiliary power
DC voltage 850 V 975 V 1100 V
PVS980-58-1818kVA-I 98.58% 98.26% 98.14%
DC voltage 893 V 997 V 1100 V
PVS980-58-1909kVA-J 98.58% 98.30% 98.20%
DC voltage 935 V 1018 V 1100 V
PVS980-58-2000kVA-K 98.60% 98.36% 98.27%
DC voltage 978 V 1039 V 1100 V
PVS980-58-2091kVA-L 98.64% 98.47% 98.36%
European efficiency with auxiliary power
DC voltage 850 V 975 V 1100 V
PVS980-58-1818kVA-I 98.43% 98.15% 97.98%
DC voltage 893 V 997 V 1100 V
PVS980-58-1909kVA-J 98.42% 98.11% 98.05%
DC voltage 935 V 1018 V 1100 V
PVS980-58-2000kVA-K 98.47% 98.18% 98.12%
DC voltage 978 V 1039 V 1100 V
PVS980-58-2091kVA-L 98.47% 98.34% 98.18%