Program number
(Job/program bit
0-7; ROB 5000/
ROB 5000 OC)
NOTE!
The allocations are identical to those in the “Job number” function (see next sec-
tion). The choice between the „program number“ and „job number“ functions is
made using mode bits 0 -2.
Pin X11/1 Job / program bit 0 Process
ROB 5000 ROB 5000 OC
0 V 24 V DC
24 V 0 V AC
Pin X11/2 Job / program bit 1 Process
ROB 5000 ROB 5000 OC
0 V 24 V DC -
24 V 0 V AC +
Pin X11/3 Job / program bit 2 Process
ROB 5000 ROB 5000 OC
0 V 24 V No cap-shaping
24 V 0 V Cap-shaping activated
Pin X11/4 Job / program bit 3 Process
ROB 5000 ROB 5000 OC
0 V 24 V Pulse ON
24 V 0 V Pulse OFF
Pulse range set-
tings
000 Set pulse range on power source
001 Setting of pulse range deactivated
010 0.2 - 2 Hz
011 2 - 20 Hz
100 20 - 200 Hz
101 200 - 2000 Hz
X11/5 Pulse range, first digit
X11/6 Pulse range, second digit
X11/7 Pulse range, third digit
Example ROB 5000:
- X11/5 is not set (= 0)
- X11/6 is not set (= 0)
- X11/7 is set (= 1)
- Frequency range 20 - 200 Hz selected