Fujitsu Airstage V series - Troubleshooting 40 - OUTDOOR UNIT Error Method: Inverter Start-Up Current Error (Only for Main Unit)

Fujitsu Airstage V series
322 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Trouble shooting 40
OUTDOOR UNIT Error Method:
Inverter Start-up Current Error
(Only for Main Unit)
Indicate or Display:
Outdoor Unit : LED1 Flash, LED5 4 Times Blink
Indoor Unit : Operation LED
ERROR CODE : E : 32
Detective Actuators:
Outdoor Unit Controller PCB circuit
Inverter PCB
Detective details:
When Start-up over current shut-down error is detected on Inverter PCB,
Inverter compressor is once stopped and restarted, then Start-up over current
Shut-down error is detected 10 times continuously at the frequency of lower
than 30Hz.
Check Point 1 :Check Filter PCB and Inverter PCB
p Check connection of Inverter PCB and Filter PCB (Loose connector, Cable cut open, etc.)
p Check Filter PCB and Inverter PCB. (PARTS INFORMATION 4)
Check Point 2 : Check Inverter Compressor
If the symptom does not change with above Check 1, check Inverter Compressor
since the Inverter Compressor may be defective. (PARTS INFORMATION 1,3)
OK
Forecast of Cause : 1. Outside cause 2. Electrical Component connection failure 3. Controller PCB failure
06-50
Blink, Timer LED 3Time Blinks,
Swing LED 3Time Blinks,