Check Point : ARXA36 / 45LATF
p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
5.86 ± 8%Pink - Violet
5.86 ± 8%Violet - Blue
5.86 ± 8%Red - Pink
13.0 ± 8%Red - Black
White - Red
Read Wire
19.7 ± 8%
Resistance value(20°C)
Low(Violet)
Med(Pink)
Hi(Red)
(Black)
(White)
(AC)
Thermal protector
(150°C)
Super low(Blue)
Check Point : ARXC36LATF
p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
12.9 ± 8%Violet - Blue
11.2 ± 8%Red - Violet
16.5 ± 8%Red - Black
White - Red
Read Wire
13.4 ± 8%
Resistance value(20°C)
Low(Blue)
Med(Violet)
Hi(Red)
(Black)
(White)
(AC)
Thermal protector
(150°C)
Low(Blue)
Int.1(Violet)
Hi(Red)
(Black)
(White)
(AC)
Thermal protector
( °C)
Check Point : ARXC45 / 60LATF
p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
6.1 ± 8%Violet - Blue
6.1 ± 8%Red - Violet
9.78 ± 8%Red - Black
White - Red
Read Wire
6.84 ± 8%
Resistance value(20°C)
06-103