02-43
2-4-5 Network Convertor
1. Control input
(Operation / Stop)
Indoor units that connected to network convertor can be controlled all operation / all stop
by this input.
CN105
Ch1
Indoor
Unit
All operation
CN105
(RED)
DIP SW108-1
(1) Input select
(2) In the case of "Edge" input
CONNECTOR INPUT SIGNAL COMMAND
CN105
(RED)
All operation
All stop
OFF ON
ON OFF
ON
OFF
CN105
Ch1
Indoor
Unit
All operation
All stop
(3) In the case of "Pulse" input
DIP SW108-2 Input select
"Edge"
"Pulse"
ON
ON
CN105
Ch2
OFF
ON
Ch1
CONNECTOR INPUT SIGNAL COMMAND
CN105
(RED)
All operation
All stop
OFF ON
Ch1
Ch2
OFF ON
All stop
On
Off
On
Off
The width of pulse must be longer than 200ms.
Ch2
3
2
1
P.C.B
Ch1
. . .
. . .
. . .
CN105 (RED)
CN108 (BLK) CN109
EXT IN
EXT OUT1
EXT OUT2
3 2 1
1 2 3
1 2 3
The connector positions and pin number of
network convertor (UTR-YSSA) for external
input and output are shown in the right figure.
*UTR-YRDA doesn't provide the function of
external Input/Output.
SW107 SW108 SW109 SW103
SW110 SW111
D129

Table of Contents