<< SIMPLE REMOTE CONTROLLER >>
Run [Self-Diagnosis] if [EE] flashes on the display of the remote controller.
The error of the indoor unit is displayed.
I. Stop the air conditioner operation.
II. Press the button and the button at the same time for more than 5 seconds to
start the self-diagnosis.
*Please refer to the error codes as follows.
III. Press the button and the button at the same time for more than 5 seconds to
stop the self-diagnosis.
Outdoor unit Error
Communication Error between Main
PCB & Transmission PCB
Network communication Error
Standard wired token Error
Standard wired remote Error
Indoor fan motor Error
Drain Error
ERROR CONTENT
6
5
4
3
2
1
Trouble
Shooting
E : 32
E : 21
E : 1F
E : 18
E : 18
E : 13
E : 11
ERROR
CODE
Heat Ex. Inlet sensor error
Heat Ex. Middle Sensor
Error
Room sensor Error
EEPROM access Error
Power frequency Error
Model information Error
No Error
ERROR CONTENT
7E : 00
8E : 02
9E : 04
10E : 06
12E : 09
11E : 0A
13 ~ 48E : 0b
Trouble
Shooting
ERROR
CODE
<< WIRED REMOTE CONTROLLER >>
Run [Self-Diagnosis] if [E:EE] flashes on the clock display of the remote controller.
The error of the indoor unit is displayed.
I. Stop the air conditioner operation.
II. Press the Set Temperature buttons and at the same time for more than 5
seconds to start the self-diagnosis.
*Please refer to the error codes as follows.
III. Press the Set Temperature buttons and at the same time for more than 5
seconds to stop the self-diagnosis.
6-2-2 Remote Controller
06-05

Table of Contents