Check Point : ARXB25 / 30LATF
p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
12.9 ± 8%Pink - Violet
12.9 ± 8%Violet - Blue
21.3 ± 8%Red - Pink
37.3 ± 8%Red - Black
White - Red
Read Wire
44.8 ± 8%
Resistance value(20°C)
Low(Violet)
Med(Pink)
Hi(Red)
(Black)
(White)
(AC)
Thermal protector
(150°C)
Super low(Blue)
Check Point : ARXB36LATF, ARXA25 / 30LATF
p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
8.96 ± 8%Pink - Violet
8.96 ± 8%Violet - Blue
8.96 ± 8%Red - Pink
29.1 ± 8%Red - Black
White - Red
Read Wire
50.9
±
8%
Resistance value(20°C)
Low(Violet)
Med(Pink)
Hi(Red)
(Black)
(White)
(AC)
Thermal protector
(150°C)
Super low(Blue)
Check Point : ARXB45LATF
p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
7.9 ± 8%Pink - Violet
7.9 ± 8%Violet - Blue
11.4 ± 8%Red - Pink
23.8 ± 8%Red - Black
White - Red
Read Wire
40.3 ± 8%
Resistance value(20°C)
Low(Violet)
Med(Pink)
Hi(Red)
(Black)
(White)
(AC)
Thermal protector
(150°C)
Super low(Blue)