EasyManuals Logo

Fujitsu Airstage V series User Manual

Fujitsu Airstage V series
322 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #38 background imageLoading...
Page #38 background image
02-25
Pipe Length Setting SW ( Only for master unit )
SW6 setting
Applicable piping length
Standard
SW6-1
OFF
Short
Medium
Set up SW6-1 and SW6-2 to match up with the pipe length as follows.
OFF
ON
ON
SW6-2
OFF
OFF
ON
ON Long
Remarks: Pipe Length(m)
40<Pipe Length<80
Pipe Length<40
80<Pipe Length<120
120<Pipe Length<150
=
=
=
=
PIPING LENGTH SETTING SW
( Factory setting)
SW5 setting
Cooling Capacity shift SW ( Only for master unit )
Heating Capacity Shift SW ( Only for master unit )
This setting makes it possible to vary the outflow air temperature with in the range of about
2 degrees, by which 15% capacity increase and energy saving operation are realized.
SW 5-2
SW 5-1
OFF
OFF
ON
OFF
COOLING CAPACITY SHIFT SW
( Factory setting)
OFF
ON
ON
ON
Capacity shift
Normal mode
Save energy mode
High power mode 1
High power mode 2
SW 5-4SW 5-3
OFF OFF
ON
OFF
HEATING CAPACITY SHIFT SW
( Factory setting)
OFF
ON
ON ON
Capacity shift
Normal mode
Save energy mode
High power mode 1
High power mode 2
SW7 setting
System type of the outdoor unit (Setting for master and slave unit)
The system type of the outdoor unit can be selected by setting up SW7-1 and SW7-2 as follows.
If the total capacity of the connected indoor units is less than 90% of the outdoor unit capacity, set this switch to ON.
OFF
System typeSW7-1
Heat pump
OUTDOOR UNIT SYSTEM TYPE SELECTION
( Factory setting)
Cooling onlyON
OFF
Indoor unit connecting capacitySW7-3
90% or more
INDOOR UNIT SMALL CAPACITY SETTING
( Factory setting)
less than 90%ON
Dip SW 7-2, SW7-4 setting forbidden
SW7-2
SW7-4
OFF
OFF
SW6-3 OFF
SW6-4 OFF
Indoor unit small capacity setting (Only for master unit)
Dip SW 6-3, SW6-4 setting forbidden
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
Outdoor unit
Separation
Tube
Pipe length
Pipe length:
Between the master outdoor unit and
the farthest indoor unit

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu Airstage V series and is the answer not in the manual?

Fujitsu Airstage V series Specifications

General IconGeneral
BrandFujitsu
ModelAirstage V series
CategoryAir Conditioner
LanguageEnglish

Related product manuals