Check Point : ARXC90LATF
p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
26.1 ± 8%W(Black) - U(Red)
26.1 ± 8%V(White) - W(Black)
U(Red) - V(White)
Read Wire
26.1 ± 8%
Resistance value(20°C)
Check Point : ASYA18 / 24 / 30LATF
p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
277 ± 8%Blue - Red
21.0 ± 8%Black - Blue
White - Red
Read Wire
129
±
8%
Resistance value(20°C)