LED2,3,4,5,6
LED6
LED5
LED4
LED3
LED2
1 ~ 121 time flashIndoor unit Error **
472 times flashSlave unit Error *
415 times flashInverter normal current value Error *
426 times flashInverter communication Error *
459 times flashNetwork communication Error *
448 times flashCommunication error between Outdoor units
404 times flashInverter star up current value Error *
393 times flashEEPROM Access Error
437 times flashParallel communication Error
371 time flashReverse phase, missing phase wire Error
364 times flashCurrent sensor Error *
382 times flashInverter Error *
4610 times flashMaster unit, Slave unit set-up Error
48Continuously lightingInitial setting Error
353 times flashSuction pressure sensor Error
341 time flashDischarge pressure sensor Error
3312 times flashOutdoor temp. sensor Error
3211 times flashSuction gas temp. sensor Error
3110 times flashLiquid pipe temp. sensor 2 Error
309 times flashLiquid pipe temp. sensor 1 Error
29-1
29-2
8 times flashSub-cool Heat Exchanger Gas output temp. sensor Error
Sub-cool Heat Exchanger Gas inlet temp. sensor Error
287 times flashRCV Liquid surface detection sensor 3 (Higher limit) Error
276 times flashRCV Liquid surface detection sensor 2 (Middle limit) Error
265 times flashRCV Liquid surface detection sensor 1 (Lower limit) Error
254 times flashHeat Ex. Liquid Temperature Sensor Error
243 times flashDischarge Temp Sensor 3 Error
232 times flashDischarge Temp Sensor 2 Error
221 time flashDischarge Temp Sensor 1 Error
219 times flashPomp down Error
208
5011 times flash
4910 times flash
times flashLow pressure Error
197 times flashHigh pressure Error
186 times flashDischarge Temperature 3 Error
175 times flashDischarge Temperature 2 Error
164 times flashDischarge Temperature 1 Error
153 times flashCompressor 3 Error
142 times flashCompressor 2 Error
131 time flash
LED1
Continuous
flash
Compressor 1 Error
Trouble
shooting
LED Flashing PatternError Contents
All compressor of 1 unit Error
4-way valve Error
13 times flash
*
Error with occurs on Master unit only
** It indicates when the error signal is received from one of Indoor units within the same refrigerant system.
Please refer to TROUBLE LEVEL OF SYSTEM for Outdoor unit condition of following errors.
Please refer to previous page for flashing pattern.
06-06
6-2-3 Outdoor Unit Display
3 times flash
Indoor unit shortage Error
12-A

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu Airstage V series and is the answer not in the manual?

Fujitsu Airstage V series Specifications

General IconGeneral
BrandFujitsu
ModelAirstage V series
CategoryAir Conditioner
LanguageEnglish

Related product manuals