Loading...
Red - Black
Red - White
Blue - Red
Read Wire
15%
38.5
82.0
15%
22.0 15%
Resistance value
BLUE
RED
BLACK
WHITE
YELLOW
at 20°C
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Pr
Red - Black
Red - White
Blue - Red
Read Wire
5%
45.0
59.5
5%
22.5 5%
Resistance value
BLUE
RED
BLACK
WHITE
YELLOW
at 20°C
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Pr
SERVICE PARTS INFORMATION 12
Outdoor Unit Fan Motor
Check Point : AJ*A90/72L / AJ*A90/72U
Check Point : AJ*126L / AJ*126U
06-105