7-2 CHARACTERISTICS OF SENSORS
07-05
7-2-1 Pressure Sensor
When installing the pressure sensor, connect a lead wire to the PCB ( ), thereafter connect the other end
of a lead wire to the pressure sensor ( ). When disconnecting, do the opposite procedure.
Be careful not to install other than above procedure, otherwise the pressure sensor can be failed.
0 2.5 5.0
1
3
5
Pressure
Output
MPa
V
1. Characteristics of pressure sensor
2. Check point of replacing pressure sensor
Pressure sensor
Printed circuit board
Lead wire
Pressure
(MPa)
Output
0.00
1.00
0.10
1.08
0.20
1.16
0.30
1.24
0.40
1.32
0.50
1.40
0.60
1.48
0.70
1.56
0.80
1.64
0.90
1.72
1.00
1.80
1.20
1.96
1.40
2.12
1.60
2.28
1.80
2.44
2.00
2.60
2.20
2.76
2.40
2.92
2.60
3.08
2.80
3.24
3.00
3.40
3.20
3.56
3.40
3.72
3.60
3.88
3.80
4.04
4.00
4.20
Output voltage of the pressure sensors ( HP,LP )
(V)
Pressure
(MPa)
Output
(V)
4.20
4.36
4.40
4.52
4.60
4.68
4.80
4.84
5.00
5.00
Pressure
(MPa)
Output
(V)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu Airstage V series and is the answer not in the manual?

Fujitsu Airstage V series Specifications

General IconGeneral
BrandFujitsu
ModelAirstage V series
CategoryAir Conditioner
LanguageEnglish

Related product manuals