5-2 MASTER CONTROL
05-02
5-2-1 Operation Mode Control
(2) Cool, Fan, Dry and Heat Mode
Indoor fan motor
Operates according to
the AIR FLOW-MODE
setting.
Operates according
to the AIR FLOW-
MODE setting.
See the fan control
page.
Cool Fan Dry
Drain pump
Turns ON-OFF by the drain pump control function
Electrical
expansion valve
Pulse controlled by
the temperature differ-
ence calculation and
frost prevent fuction
Stop pulse
Each operation mode is controlled as below.
(1) Stop mode
Indoor fan motor : OFF
Electric expansion valve
Drain pump
: Stop pulse
: Turns ON-OFF by the drain pump control function
Operates according to
the AIR FLOW-MODE
setting, and besides
cold air prevention
operation
Pulse controlled by
the temperature dif-
ference calculation
and frost prevent
function
HEAT
Pulse controlled by
the temperature dif-
ference.
5-2-2 Auto Changeover
Yes
Yes
Yes
NO
Operation flow chart
START
Room temp.
Ts+2 ?
Room temp.
Ts+1 ?
COOLING OPERATION
DRY OPERATION
Yes
NO
NO
NO
Cool
Dry
Room temp.
Ts+2 ?
Refrigerant
circulation
stopped?
AUTO CHANGEOVER operation (COOLING ONLY TYPE )
TS : Setting temperature
(1) When the indoor unit starts the operation
at “AUTO" or it is switched to “AUTO” from
other modes, if the room temperature is
higher than the set temperature +
(Room temp. Set temp.(Ts) + ),
"COOL" operation will start automatically.
2
2
(2)
(3)
2
When the room temperature increases
up to the set temp. (Ts) + during the
"DRY" operation, the indoor unit will
switch to "COOL" operation automatically.
1
When the room temperature decreases
under the set temp. (Ts) + during the
"COOL" operation, the indoor unit will
switch to "DRY" operation automatically.
(4)
When the indoor unit starts the operation
at “AUTO" or it is switched to “AUTO” from
other modes, if the room temperature is
lower than the set temperature +
(Room temp. Set temp.(Ts) + ),
"DRY" operation will start automatically.
2
2
Ts+2
Ts
Ts+1
Cool
Dry
The cases of (1) and (4)
Cool
DR
Y
The cases of (2) and (3)
Refrigerant
circulation
started?
NO
Yes
(due to temp.)
(due to temp.)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu Airstage V series and is the answer not in the manual?

Fujitsu Airstage V series Specifications

General IconGeneral
BrandFujitsu
ModelAirstage V series
CategoryAir Conditioner
LanguageEnglish

Related product manuals