SERVICE PARTS INFORMATION 13
Resistor, Cement
Check Point 1 : Appearance check
Check Point 2 : Electric check
Set the tester to the "Resistance" mode, and measure the resistance value between the terminals.
(No polarity)
Judge the result of as follows:
5.32 to 5.88 : Normal
Other than the above : Deteriorated, defective
No fissures, breaks, damage, etc. at the body and terminals section?
1. Surge prevention resistor (connected to power relay)
06-106
SERVICE PARTS INFORMATION 14
Reactor
Check Point 1 : Appearance check
Check Point 2 : Electric check
Set the tester to the "Resistance" mode, and check for open/short between both ends of the reactor wire
(or connector).
Judge the result of as follows:
Short : Normal
Open : Abnormal (open)
No fissures, breaks, damage, etc. at the body and winding section, terminals section?