Check Point : ABYA30 / 36 / 45 / 54LATF
p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
31.9 ± 10%
Read Wire
22.8 ± 10%
Resistance value(20°C)
Check Point : AUXB07 / 09LATF
p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
99.6 ± 8%Red - Violet
99.6 ± 8%Violet - Blue
329 ± 8%Blue - Black
White - Red
Read Wire
658 ± 8%
Resistance value(20°C)
(Violet)
(Blue)
(Red)
(White)
(AC)
(Black)
Check Point : AUXB12 / 14LATF
p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
06-99
(AC)
Thermal protector
120°C
Pr
12
3
1 3
2 3
103 ± 8%Violet - Blue
103 ± 8%Red - Violet
541 ± 8%Red - Black
White - Red
Read Wire
455 ± 8%
Resistance value(20°C)
Low(Blue)
Med(Violet)
Hi(Red)
(Black)
(White)
(AC)
Thermal protector
(140°C)