Outdoor Unit Error *
Network Communication Error
Main PCB - Transmission PCB
Communication Error
Standard Wired Token Error
Standard Wired Remote Control
Error
Indoor Fan Motor Error
Drain Error
Heat Ex. Middle Sensor Error
Heat Ex. Inlet Sensor Error
Room Temp. Sensor Error
EEPROM Access Error
Power Freq. Error
Model Information Error
Error Contents
13 ~ 48
OFF3 times flash3 times flashContinuous flash
12
OFF1 time flash5 times flashContinuous flash
11
OFFOFF6 times flashContinuous flash
10
OFF4 times flashContinuous flash5 times flash
9
OFF1 time flashContinuous flash5 times flash
8
OFFOFFContinuous flash6 times flash
7OFFOFFContinuous flash4 times flash
6
OFF2 times flashContinuous flash3 times flash
5
OFF1 time flashContinuous flash3 times flash
4
OFFOFFContinuous flash2 times flash
3
OFF1 time flash4 times flashContinuous flash
2
Continuous
flash
Continuous
flash
Continuous flashContinuous flash
1
OFFOFFContinuous flashContinuous flash
Trouble
shooting
Horizontal
Swing LED
Vertical
Swing LED
Timer LEDOperation LED
* Depending on contents of Outdoor unit, it may not indicate. (Refer to “TROUBLE LEVEL OF SYSTEM”)
Error Indication Flashing Pattern
Indoor/Outdoor LED Cont. Flash
0.1 sec ON / 0.1 sec OFF flashing
Outdoor LED Flash (1 to 12 times)
0.3 sec ON / 0.3 sec OFF flashing
Indoor LED Flash (1 to 6 times)
0.5 sec ON / 0.5 sec OFF flashing
Please refer the flashing pattern as follows.
06-04
6-2 ABNORMAL OPERATION
6-2-1 Indoor Unit Display