02-44
2. Output
This output indicates the indoor unit's "Operation" or "Stop" status.
Indoor
Unit
Operation
Stop
Short
Open
CN108
(BLK)
(1) Operation display (EXT OUT1)
CN108
(BLK)
P.C.B
Open
Short
CN108
(BLACK)
Indoor units "Stop"
Indoor units "Operation"
CONNECTOR
OUTPUT
SIGNAL
STATUS
ON /OFF
Indicator
Com
(2) Error display (EXT OUT2)
This output indicates the indoor unit's "Normal" or "Error" status.
CN109
(WHITE)
All of the indoor units "Normal"
At least one more indoor units "Error"
CONNECTOR
STATUS
Indoor
Unit
Error
Normal
CN109
(WHITE)
3. Parts
Following cord (service parts) is required. Please use the parts number shown below
to order the cord from your sales representative.
9368779009
Name and shapes Q'ty Parts No.
1
EXTERNAL
INPUT
WIRE
* 1
* 2
* 1 Always insert a diode on both ends of relay coil.
* 2 Pin 2 - Pin 3 Max 15V, 50mA
OUTPUT
SIGNAL
Open
Short
Short
Open
2
1
3
CN109
(WHITE)
P.C.B
Error
Indicator
Com
* 1
* 2
* 1 Always insert a diode on both ends of relay coil.
* 2 Pin 2 - Pin 3 Max 15V, 50mA
2
1
3
Usage
For control
input and output port