BACnet Object list
• Type: Indoor
BACnet
object
type
Code (II)
Function name
Unit
Inactive Active
Text-1 Text-2 Text-3 Text-4 Text-5 Text-6 Text-7
AI
10 Set temp. status Degree
11 Space temp. Degree
12 Auto temp. (Low limit status) Degree
13 Auto temp. (High limit status) Degree
14 Cool/Dry temp. (Low limit status) Degree
15 Cool/Dry temp. (High limit status) Degree
16 Heat temp. (Low limit status) Degree
17 Heat temp. (High limit status) Degree
AO
10 Temp. setting Degree
11 Auto temp. (Low limit setting) Degree
12 Auto temp. (High limit setting s) Degree
13 Cool/Dry temp. (Low limit setting) Degree
14 Cool/Dry temp. (High limit setting) Degree
15 Heat temp. (Low limit setting) Degree
16 Heat temp. (High limit setting) Degree
AV 10 ECA* operation data
BI
10
Operation status OFF ON
14 Filter sign status Unsigned Signed
15 Indoor unit error status Normal Fault
16 Anti-freeze operation status Reset Set
17 SAVE operation status Normal SAVE
18 Forced thermostat off status Reset Set
19 Emergency stop status Normal Stop
20 Mode mismatch status Normal Mismatch
21 Protect anti-freeze status Reset Set
22 Temp. limit valid status Invalid Valid
BO
10 Operation setting OFF ON
14 Filter sign resetting Reset Not reset
15 Anti-freeze operation setting Reset Set
16 SAVE operation setting Reset Set
17 Forced thermostat OFF setting Reset Set
18 Emergency stop setting Reset Set
19 Temp. limit valid setting Invalid Valid
MI
10 Operation mode status COOL HEAT FAN DRY AUTO
11 Fan speed status LOW HIGH MED AUTO QUIET MED-LOW MED-HIGH
12 Indoor unit error code Refer to FGL original error code
13 R.C. prohibition status Refer to R.C. prohibition setting chart
14 Vertical airflow direction status 1 2 3 4 SWING
15 Horizontal airflow direction status 1 2 3 4 5 SWING
16 Special driving status Normal Defrost Oil recovery
17 Managed mode None Master Slave External
MO
10 Operation mode status COOL HEAT FAN DRY AUTO
11 Fan speed setting LOW HIGH MED AUTO QUIET MED-LOW MED-HIGH
12 R.C. prohibition setting Refer to R.C. prohibition setting chart
13 Vertical airflow direction setting 1 2 3 4 SWING
14 Horizontal airflow direction setting 1 2 3 4 5 SWING
TL 10 ECA* operation data log
*: Electricity charge apportionment
• Type: Outdoor
BACnet
object
type
Code (II)
Function name
Unit
Inactive Active
Text-1 Text-2 Text-3 Text-4 Text-5 Text-6 Text-7 Text-8
BI
30 Outdoor unit error status Normal Fault
31 Forced off status Reset Set
BO 30 Forced off setting Reset Set
MI
30
Outdoor unit priority operation status*
1
COOL HEAT Neautral None
31 Outdoor error code Refer to FGL original error code
32 Capacity save status Not set 100% 90% 80% 70% 60% 50% 40%
33
Outdoor low noise operation status*
2
MO
30
Outdoor low noise operation status*
3
Stop
Level-1
Quiet
Level-1
Ability
Level-2
Quiet
Level-2
Ability
Level-3
Quiet
Level-3
Ability
32 Capacity save setting Not set 100% 90% 80% 70% 60% 50% 40%
• *1: Priority operation status is for Heat pump type VRF. In other types of systems, this status is not necessary.
• *2: Refer to the “Outdoor unit low nose operation value table” for the texts used with the “Outdoor low noise operation status”.
• *3: Outdoor unit firmware may need to be updated for this function to work. For details, contact your local sales company.
3-10. BACnet gateway (Software: UTY-ABGXZ1) - (05-176) - 3. Adaptor/Convertor units