Type: Gateway
BACnet
object
type
Code (II)
Function name
Unit
Inactive Active
Text-1 Text-2 Text-3 Text-4 Text-5 Text-6
Device Device information
BI
00 Lon network adapter error status Normal Abnormal
01 Gateway status error Normal Abnormal
02 ES status Not used Energy saving
BO 02 ES setting Not used Energy saving
MI
00 Lon network adapter error code Refer to FGL original error code
01 Gateway error code Refer to FGL original error code
02 ECA* status Invalid
Invalid
(Stop)
Include indoor
unit only
Exclude indoor
and RB unit
Include indoor
and RB unit
Include RB unit
MO 01 ECA* setting Stop
Include indoor
unit only
Exclude indoor
and RB unit
Include indoor
and RB unit
Include RB unit
Notification 00—99 Notification class
CAL
00 Calendar “Holiday-1”
01 Calendar “Holiday-2”
02—32 Calendar “Special day-1”—”Special day-30”
Schedule 00—99 Schedule timer
*: Electricity charge apportionment
NOTES:
To protect the compressor of the outdoor unit, carefully read and understand the following cau-
tions that may affect the operation of compressor before executing the setting.
CAUTION
When regularly making the following settings to the same outdoor unit by using schedule
function etc., leave the following interval.
<Corresponding function>
More than 6 minutes
must elapse
More than 3 minutes
must elapse
• Set outdoor unit forced off mode
• Reset outdoor unit forced off mode
When performing periodical settings like schedule settings for the following functions, per-
form the setting to all indoor units in the same refrigerant system simultaneously, conforming
to the timing restriction described below.
<Corresponding function>
More than 10 minutes
must elapse
More than 10 minutes
must elapse
• Stop operation
• Set indoor unit forced thermostat off mode
Start operation
• Release indoor unit forced thermostat off mode
Forced thermostat off instruction, outdoor unit forced off instruction, and capacity saving setting
Only one equipment can send these instructions for each refrigerant system.
When these instructions are sent by multiple equipment (eg. from System controller and BAC-
net gateway at the same time), the system may not respond as instructed or may cause mal-
function.
The electricity charge apportionment function of VRF system can only be performed from one
equipment simultaneously. Therefore, ECA setting, required to be set before performing elec-
tricity charge apportionment, can only be sent from one equipment simultaneously.
The energy saving function of VRF system can only be performed from one equipment simulta-
neously. Therefore, ES setting, required to be set before performing energy saving, can only be
sent from one equipment simultaneously.
3-10. BACnet gateway (Software: UTY-ABGXZ1)
- (05-177) - 3. Adaptor/Convertor units