Refrigerant system examples
NOTE: For cooling capacity range of connectable indoor units, refer to "Refrigerant system" on
page 06-1.
Example 1 (OK)
Outdoor unit
Indoor unit 1 Indoor unit 2
Capacity ratio 80%
Model name
Cooling
capacity
Total
capacity
Connectable
indoor unit
capacity
Judge
Min. Max.
(kW)
Outdoor unit
AJ072LELDH
22.4 22.4
(2) 50%
11.2
(3) 150%
33.6
(2) ≤ (1) ≤ (3)
11.2 < 18.0 < 33.6 → OK
Indoor unit 1 AUXK030GLEH 9.0
(1) 18.0
Indoor unit 2 AUXK030GLEH 9.0
Example 2 (OK)
Outdoor unit
Indoor unit 1 Indoor unit 2 Indoor unit 3
Capacity ratio 112%
Model name
Cooling
capacity
Total
capacity
Connectable
indoor unit
capacity
Judge
Min. Max.
(kW)
Outdoor unit
AJ072LELDH
22.4 22.4
(2) 50%
11.2
(3) 150%
33.6
(2) ≤ (1) ≤ (3)
11.2 < 25.1 < 33.6 → OK
Indoor unit 1 AUXK030GLEH 9.0
(1) 25.1Indoor unit 2 AUXK030GLEH 9.0
Indoor unit 3 AUXB024GLEH 7.1
1-1. Refrigerant system - (06-2) - 1. System design
SYSTEM
DESIGN
SYSTEM
DESIGN