Example 3 (Prohibited)
Outdoor unit
Indoor unit 1 Indoor unit 2 Indoor unit 3
Capacity ratio 175%
Model name
Cooling
capacity
Total
capacity
Connectable
indoor unit
capacity
Judge
Min. Max.
(kW)
Outdoor unit
AJ072LELDH
22.4 22.4
(2) 50%
11.2
(3) 150%
33.6
(3) < (1)
33.6 < 39.2 → Prohibited
Indoor unit 1 AUXK054GLEH 14.0
(1) 39.2Indoor unit 2 AUXK054GLEH 14.0
Indoor unit 3 AUXK036GLEH 11.2
Example 4 (OK)
Outdoor unit
Indoor unit 1
Capacity ratio 63%
Model name
Cooling
capacity
Total
capacity
Connectable
indoor unit
capacity
Judge
Min. Max.
(kW)
Outdoor unit
AJ072LELDH
22.4 22.4
(2) 50%
11.2
(3) 150%
33.6
(2) ≤ (1) ≤ (3)
11.2 < 14.0 < 33.6 → OK
Indoor unit 1 AUXK054GLEH 14.0 (1) 14.0
1-1. Refrigerant system - (06-3) - 1. System design