Low static pressure duct (Slim duct)/Slim concealed floor type
Ceiling concealed setting
Drain hose
Arrange the drain hose
lower than this position
Drain cap
Supporter
Prohibited
Trap
Ï
Rise
Ï
Air bleeding
Ï
Locally arranged pipe
Max. 300 mm
VP25
(O.D. 32 mm
or more)
Supporter
Gap of 1.5 to 2 m
Prohibited
Air bleeding
Rise
Trap
Horizontal or
upward gradient
1.5 m to 2.0 m
Max. 700 mm
Ï
Ï
Ï
Floor standing concealed setting
Prohibited
Trap
Drain cap
Rise
Install the drain pipe with downward gradient (1/100 or more) and so there are no rises or traps
in the pipe.
Use general hard polyvinyl chloride pipe (VP25) (O.D. 32 mm) and connect it with adhesive
(polyvinyl chloride) so that there is no leakage.
When the pipe is long, install supporters.
Do not perform air bleeding.
Always heat insulate the indoor side of the drain pipe.