Low static pressure duct type (High efficiency)
Attached band
Supporter
Attached drain hose
Downward gradient
1/100 or more
Arrange the drain hose
lower than this position
1.5 to 2.0 m
Drain hose
Air bleeding
Rise
Trap
ÏÏ
Ï
Prohibited
There is a drain port on the left and right sides. Select the drain port to match the local conditions.
Nylon fastener
Drain port Drain cap
CAUTION
• Always check that the drain cap is installed to the unused drain port and fastened with the nylon
fastener.
• If the drain cap is not installed, or is not sufficiently fastened by the nylon fastener, water may
drip during the cooling operation.
5-2. Indoor unit - (06-72) - 5. Drain connection