¢ Indoor unit addresses and setting ranges
Setting
Setting
range
Type of switch Remarks
D
Refrigerant circuit
address
00—99
Manual address setting:
Arbitrary numbers can be set in
range of 00—99.
Setting example
01
Wireless R. C.:
This switch is set to 00 at factory
setting.
Refer to "Address setting by
wireless remote controller" on
page 07-16.
Wired R. C. (3-wire type):
This switch is set to 00 at factory
setting.
Refer to "Address setting by
wired remote controller (UTY-
RNK)" on page 07-27.
Simple R. C.:
This switch is set to 00 at factory
setting.
Refer to "Address setting by
simple remote controller (UTY-
RSR and UTY-RHR)" on
page 07-32.
Wired R. C. (2-wire type):
This switch is set to 00 at factory
setting.
Refer to "Address setting by
wired remote controller (Touch
panel) (UTY-RNRZ)" on
page 07-45.
Automatic address setting:
This switch is set to 00 at factory
setting.
Refer to "Automatic address
setting of indoor unit" on page
07-59.
E Indoor unit address 00—63
Manual address setting:
Arbitrary numbers can be set in
range of 00—63.
Setting example
12
Wireless R. C.:
This switch is set to 00 at factory
setting.
Refer to "Address setting by
wireless remote controller" on
page 07-16.
Wired R. C. (3-wire type):
This switch is set to 00 at factory
setting.
Refer to "Address setting by
wired remote controller (UTY-
RNK)" on page 07-27.
Simple R. C.:
This switch is set to 00 at factory
setting.
Refer to "Address setting by
simple remote controller (UTY-
RSR and UTY-RHR)" on
page 07-32.
Wired R. C. (2-wire type):
This switch is set to 00 at factory
setting.
Refer to "Address setting by
wired remote controller (Touch
panel) (UTY-RNRZ)" on
page 07-45.
Automatic address setting:
This switch is set to 00 at factory
setting.
Refer to "Automatic address
setting of indoor unit" on page
07-59.
F
Remote controller
address
00—15
Manual address setting:
3-wire type R. C. can be set in
range of 0—15.
Setting example
10
Automatic address setting:
This switch is set to 00 at factory
setting.
2-wire type only.
1-2. Address setting - (07-5) - 1. System settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS