¢ Addresses and setting ranges for controllers, convertors or
other devices
Unit Setting
Setting
range
Type of switch Setting references
Touch panel
controller
G
Controller
address
00—15
*
1
"Touch panel controller"
on page 07-118"Touch
panel controller" on
page 07-118
Network converter H
Convertor
address
00—15
*
1
"Network convertor
(UTY-VTGX, UTY-
VTGXV)" on page 07-
129 and "Network
convertor (UTY-
VGGXZ1)" on page 07-
131
Refrigerant
circuit address
00—99
Setting
example 01
SW 110 SW 111
(10 digit) (1 digit)
Group remote
controller
I
Group remote
controller
address
00—03
"Group remote
controller" on page 07-
116
Wired, simple
remote controller
(3-wire type)
J
Dual remote
control
ON/OFF Switch 2 of DIP switch 1
"Wired remote controller
(UTY-RNK)" on page
07-112
"Simple remote
controller (UTY-RSK,
UTY-RHK)" on page
07-114
Signal amplifier K
Signal amplifier
address
1—8
Manual address setting
"Signal amplifier" on
page 07-133
Automatic address setting:
This switch is set to 1 at factory
setting.
"Automatic address
setting of signal
amplifier" on page 07-
57
Modbus converter Q
Controller/
convertor
address
00—15
*
1
"Modbus converter for
VRF" on page 07-
138"Modbus converter
for VRF" on page 07-
138
Network converter
for LonWorks
M
"Network converter for
LonWorks" on page 07-
143
Central remote
controller
N
"Central remote
controller (UTY-
DCGZ)" on page
07-119
Wired remote
controller
(2-wire type*
3
)
F
Remote
controller
address
1—32 *
2
Manual address setting
"Wired remote controller
(Touch panel)" on page
07-121 and "Wired
remote controller (UTY-
RLR)" on page 07-
125
0—15 Automatic address setting
J
Dual remote
control
ON/OFF
*
1
: The sum total of the Touch panel controller, Central remote controller, Network converter for
Group remote controller, Modbus converter, and Network converter for LonWorks is a maximum
of 16.
NOTE: For Touch panel controller, Central remote controller, Network converter for Group re-
mote controller, Modbus converter, and Network converter for LonWorks connected in
same VRF network system, set an exclusive address on each device.
*
2
: The address can be set in the range of 1 to 32. However, do not set the same number as that
for the remote controller address of an indoor unit connected using the same remote-control ca-
ble.
1-2. Address setting
- (07-6) - 1. System settings