Button name and function
Address code or function indicator on the remote controller is as shown in the figures below.
• For an outline of the address setting, refer to "Address setting" on page 07-4.
• For the details of function number and setting number used for the function setting, refer to "Func-
tion details" on page 07-108.
• It does not matter whether the refrigerant circuit address or indoor unit address is set first. (The
method shown here sets the indoor unit address first.)
• During address setting mode, indoor unit reject the any operation command from remote con-
troller.
Function number
01: Indoor unit address
02: Refrigerant circuit address
Remote controller address
Remote controller address
setting number 00 to 15
SET BACK button
Switches the remote controller
address setting number
SET TIME “<” and “>” button
Switches the function number
Setting number
Indoor unit address valid range: 00 to 63
Refrigerant circuit address valid range: 00 to 99
SET TEMP. “V” and “Λ” button
Switches the setting number
TIMER SET button
Transmits address/function setting
RELATED LINKS
"Indoor unit (setting by UTY-RNK)" on page 07-93
Entering setting mode
Hold down the 3 buttons of SET TEMP. “ “, SET TEMP. “ “, and FAN at the same time for 5 sec-
onds or longer. The setting mode will be activated.
Initial display of address setting mode
1-4. Address setting by remote controller - (07-28) - 1. System settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS