Button name and function
Address code or function indicator on the remote controller is as shown in the figures below.
For an outline of the address setting, refer to "Address setting" on page 07-4.
For the details of function number and setting number used for the function setting, refer to "Func-
tion details" on page 07-108.
It does not matter whether the refrigerant circuit address or indoor unit address is set first. (The
method shown here sets the indoor unit address first.)
During address setting mode, indoor unit reject the any operation command from remote con-
troller.
Indoor unit address valid range: 00 to 63
Refrigerant circuit address valid range: 00 to 99
Function number
Remote controller address
FAN button
Each time this button is pressed,
the fan setting changes among
“Remote controller address,
“Function number” and “Setting number.
Setting number
START/STOP button
Transmits address setting
SET TEMP.
p
and
q
button
Switches the various numbers
UTY-RSK* (With operation mode)
UTY-RHK* (Without operation mode)
01: Indoor unit address
02: Refrigerant circuit address
Remote controller address
setting number 00 to 15
Indoor unit address valid range: 00 to 63
Refrigerant circuit address valid range: 00 to 99
Function number
Remote controller address
FAN button
Each time this button is pressed,
the fan setting changes among
“Remote controller address,
“Function number” and “Setting number.
Setting number
START/STOP button
Transmits address/function setting
SET TEMP.
p
and
q
button
Switches the various numbers
01: Indoor unit address
02: Refrigerant circuit address
Remote controller address
setting number 00 to 15
RELATED LINKS
"Indoor unit (setting by UTY-RSK, UTY-RHK)" on page 07-99
Entering setting mode
Hold down the 3 buttons of SET TEMP. “ ”, SET TEMP. “ ”, and FAN at the same time for 5 sec-
onds or longer. The setting mode will be activated.