6. Confirm the selected indoor unit address data by pressing the START/STOP
/
button. The
data will be transferred to the indoor unit.
ERROR
GOOD
When the address data is properly set up on the indoor unit, the set number will be dis-
played. (GOOD)
When the address data is not set up correctly, “- -” is displayed. (ERROR) Back to the previ-
ous step and set up the indoor unit address data again.
Refrigerant circuit address setting
NOTE: Perform this setting on the master remote controller.
1. In initial display of the address setting mode, by pressing SET TEMP. “ ” button or SET
TEMP. “
” button, select a remote controller address. (Select the indoor unit you want to oper-
ate.)
If the indoor unit you want to operate has already been selected, skip this step.
Initial display of
address setting mode
Example: When remote controller address
“01” is selected
Remote controller address
2. Press the FAN button. “Function number” indicator flashes.
Function number
3.
Display the function number “02” by pressing SET TEMP. “ ” button or SET TEMP. “ ” but-
ton.
Function number
1-4. Address setting by remote controller
- (07-42) - 1. System settings