¢ Setting list
NOTE:
Code numbers not listed in the table blow are not available in this product. Do not set the
unsupported code numbers.
LED105
code no.
Setting mode
LED104
code no.
Setting function
Factory
setting
Remarks
0 0
Pipe length
setting
0 0
Standard
(40 to 65 m)
Pipe length means the length
between outdoor unit and the
nearest indoor unit.
0 1
Short
(less than 40 m)
0 2
Medium
(65 to 90 m)
0 3
Long 1
(90 to 120 m)
0 4 Prohibited
1 0 Prohibited
0 0 Prohibited
Setting prohibited
0 1 Prohibited
0 2 Prohibited
0 3 Prohibited
1 1
Cooling
capacity shift
0 0 Normal mode
0 1 Save energy mode
0 2 High power mode 1
0 3 High power mode 2
0 4 Prohibited
1 2
Heating
capacity shift
0 0 Normal mode
0 1 Save energy mode
0 2 High power mode 1
0 3 High power mode 2
1 3 Prohibited
0 0 Prohibited
Setting prohibited
0 1 Prohibited
1 4 Prohibited 0 0 Prohibited Setting prohibited
2 0
Switching
between batch
stop or
emergency
stop
0 0 Batch stop
This mode selects the pattern of
the stop function to be operated by
the external input terminal
(CN134).
Batch stop: The stop of all
indoor units connected to
same refrigerant system due
to input signal coming from
CN134.
0 1 Emergency stop
Emergency stop: When
emergency stop is actuated,
the indoor unit does not
accept the operation
command from the remote
controller. On the other hand,
when the emergency stop is
released (no input from
CN134), the air conditioner
does not return to the original
operation until operate indoor
unit by the remote controller.
2-1. Setting on outdoor unit PCB - (07-70) - 2. Function settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS