Chapter 2: Front panel programming
Vigilant VS1 and VS2 Technical Reference Manual 89
Option Description
Note: All base follow settings except “Head” and “Riser” can be activated by
correlation groups.
Alarm: The base activates its relay when the detector goes into alarm. The base
will not restore until the alarm event has been restored.
Alarm and verify (ALM+VFY): The base activates its relay when the detector goes
into alarm verify and continues when the detector goes into alarm. The base will
not restore until both events have been restored.
Alarm and prealarm (ALM+PALM): The base activates its relay when the detector
goes into prealarm and continues when the detector goes into an alarm. The base
will not restore until both events have been restored.
Type Select the device type based on the type of device you are programming.
Note: Available device types depend on the device and the marketplace selected
for the panel. Some device types are not available in some marketplaces. For this
reason, the LCD listing for the selected device may differ from this table.
Note: To correlate device types with personality codes when programming
Signature Series devices, see Appendix E “Device types to personality codes
correlation” on page 257.
Photo detector
Smoke: For smoke detectors and contact devices. All activations are
immediately considered as alarms. Circuit cannot be restored until devices are
restored to normal and the panel is reset.
Smoke verified: For smoke detectors and contact devices. Two-wire smoke
detector activations are verified (delayed and confirmed) before activating an
alarm. Four-wire smoke detectors and contact devices are not verified and
immediately considered as alarms. Circuit cannot be restored until devices are
restored to normal and the panel is reset.
Supervisory latching: For supervisory devices. Momentary activation of
normally open devices immediately places the panel in a supervisory state
and turns on supervisory LEDs and relays. Circuit cannot be restored until
devices are restored to normal and the panel is reset.
Supervisory nonlatching: For supervisory devices. Momentary activation of
normally open devices immediately places the panel in a supervisory state
and turns on the supervisory LED and relay. Annunciation remains active until
the input restores. The panel does not have to be reset.
Ion detector
Smoke: For smoke detectors and contact devices. All activations are
immediately considered as alarms. Circuit cannot be restored until devices are
restored to normal and the panel is reset.
Smoke verified: For smoke detectors and contact devices. Two-wire smoke
detector activations are verified (delayed and confirmed) before activating an
alarm. Four-wire smoke detectors and contact devices are not verified and
immediately considered as alarms. Circuit cannot be restored until devices are
restored to normal and the panel is reset.
Supervisory latching: For supervisory devices. Momentary activation of