Chapter 2: Front panel programming
Vigilant VS1 and VS2 Technical Reference Manual 59
Dialer options
Table 18 describes the options used to set up the dialer.
Table 18: Auto programming — Dialer options [1]
Option Description
Account 1 Account ID: Enter the four-digit ID code for account 1
(Note: If you do not change the default of FFFF, no
events will be sent.)
Primary receiver number: Enter the primary
receiver’s phone number. Up to 20 digits (0-9, *, #,
and ,). The comma causes a two-second delay in
dialing. The number or hash symbol (#) and the
asterisk symbol (*) are used with calling feature
codes and services. Consult your telephone service
provider.
Secondary receiver number: Enter the secondary
receiver’s phone number. Up to 20 digits (0-9, *, #,
and ,). The comma causes a two-second delay in
dialing.
Format: CID
CID: Contact ID is the alarm format that the
monitoring facility (DACR) will receive. See “Default
contact ID event codes” on page 39.
Event notification: Set event notification (event
reporting) to:
Device: Only device information is reported or
transmitted, no zone information. Note: This setting
uses default device event notification settings for
reporting events. See “Factory default settings” on
page 35.
Zone: When a device is a member of a zone, only the
zone information is reported or transmitted, no
device information.
Note: This setting uses default zone event
notification settings for reporting events. See
“Factory default settings” on page 35.
Event: Only the event type (alarm, supervisory,
trouble, etc.) is reported or transmitted, no device or
zone information. Note: This setting uses the default
CMS event notification settings for reporting events.
See “Factory default settings” on page 35.
Account 1
Account ID 6769
Primary Recver# >
Secondary Recver# >
Account 2
Account ID 6769
Primary Recver# >
Secondary Recver# >
Format CID<>
Event Notif. Event>
-------------------
Save
Account 2 Account ID: Enter four-digit ID code for account 2
Primary receiver number: Enter the primary
receiver’s phone number (up to 20 digits).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Security Vigilant VS2 and is the answer not in the manual?

GE Security Vigilant VS2 Specifications

General IconGeneral
BrandGE Security
ModelVigilant VS2
CategoryControl Panel
LanguageEnglish

Related product manuals