Chapter 2: Front panel programming
60 Vigilant VS1 and VS2 Technical Reference Manual
Option Description
Secondary receiver number: Enter the secondary
receiver’s phone number (up to 20 digits).
Format: CID
CID: Contact ID is the alarm format that the
monitoring facility (DACR) will receive. See “Default
contact ID event codes” on page 39.
Event notification: Set event notification (event
reporting) to:
Device: Only device information is reported or
transmitted, no zone information. Note: This setting
uses default device event notification settings for
reporting events. See “Factory default settings” on
page 35.
Zone: When a device is a member of a zone, only the
zone information is reported or transmitted, no
device information. Note: This setting uses default
zone event notification settings for reporting events.
See “Factory default settings” on page 35.
Event: Only the event type (alarm, supervisory,
trouble, etc.) is reported or transmitted, no device or
zone information. Note: This setting uses the default
CMS event notification settings for reporting events.
See “Factory default settings” on page 35.
[1] Dialer options are displayed only if a dialer is installed on the panel.