EasyManuals Logo

GE Security Vigilant VS2 User Manual

GE Security Vigilant VS2
284 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #72 background imageLoading...
Page #72 background image
Chapter 2: Front panel programming
60 Vigilant VS1 and VS2 Technical Reference Manual
Option Description
Secondary receiver number: Enter the secondary
receiver’s phone number (up to 20 digits).
Format: CID
CID: Contact ID is the alarm format that the
monitoring facility (DACR) will receive. See “Default
contact ID event codes” on page 39.
Event notification: Set event notification (event
reporting) to:
Device: Only device information is reported or
transmitted, no zone information. Note: This setting
uses default device event notification settings for
reporting events. See “Factory default settings” on
page 35.
Zone: When a device is a member of a zone, only the
zone information is reported or transmitted, no
device information. Note: This setting uses default
zone event notification settings for reporting events.
See “Factory default settings” on page 35.
Event: Only the event type (alarm, supervisory,
trouble, etc.) is reported or transmitted, no device or
zone information. Note: This setting uses the default
CMS event notification settings for reporting events.
See “Factory default settings” on page 35.
[1] Dialer options are displayed only if a dialer is installed on the panel.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Security Vigilant VS2 and is the answer not in the manual?

GE Security Vigilant VS2 Specifications

General IconGeneral
BrandGE Security
ModelVigilant VS2
CategoryControl Panel
LanguageEnglish

Related product manuals