Chapter 2: Front panel programming
Vigilant VS1 and VS2 Technical Reference Manual 45
Device type Description
Relay silence NC For relays that open when activated and close when you press Signal
Silence.
Relay silence NO For relays that close when activated and open when you press Signal
Silence.
Supervised output For modules that output an unsynchronized signal and that do not turn
off when you press Signal Silence.
Supervised output (latched) For latched output modules that output an unsynchronized signal and
that do not turn off when you press Signal Silence.
Unlatch outputs For output modules that are configured to manually unlatch latched
outputs [1]
[1] The following output modules can be configured to unlatch latched outputs: SIGA-CT1, SIGA-CT2,
SIGA-MAB, SIGA-MCT2, SIGA-MM1, and SIGA-UM.
Table 15: Latched output device types [1]
Device type Description
Continuous Non-
Silenceable (Latched)
For Class B latched output modules that output an unsynchronized
signal. Does not follow signal silence.
Continuous Non-
Silenceable Class A
(Latched)
For Class A latched output modules that output an unsynchronized
signal. Does not follow Signal Silence.
Relay Non-Silence NC
(Latched)
For relay devices functioning as latched output devices that open when
activated. Does not follow signal silence.
Relay Non-Silence NO
(Latched) Latch
For relay devices functioning as latched output devices that close when
activated. Does not follow signal silence.
Relay Non-Silenceable
(Latched)
For Class B relay devices functioning as latched output devices. Does not
follow signal silence.
Supervised Output
(Latched)
For Class B latched output modules that output an unsynchronized
signal. Does not follow signal silence.
Supervised Outputs Class A
(Latched)
For Class A latched output modules that output an unsynchronized
signal. Does not follow Signal Silence.
[1] Table 24 on page 96 gives a full list of devices configurable as latched output devices.
Displaying the Program menu
1. Press the Menu button.
2. Choose Program.
3. Press Enter.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Security Vigilant VS2 and is the answer not in the manual?

GE Security Vigilant VS2 Specifications

General IconGeneral
BrandGE Security
ModelVigilant VS2
CategoryControl Panel
LanguageEnglish

Related product manuals