Chapter 4: Reports
Vigilant VS1 and VS2 Technical Reference Manual 173
Zone report
The panel provides a Zone report that lists all of the devices that are in a selected
zone. The report lists the devices by the device label.
To view a zone report:
1. Press the menu button and choose Reports.
2. Choose Zone.
3. Choose the zone for which you want a report.
Main Menu
Reports
Test
Control
Program
⇩
Reports
System Status
Correlation Groups
Corr Group Config
Zone
⇩
Zones
Zone 01
Zone 02
Zone 03
System Configuration report
The panel provides a System Configuration report that displays the current
configuration of the system. There are seven system configuration reports displaying
the information shown below. System configuration reports can be printed or viewed
on the LCD.
All report: Displays all panel, device, loop, zone, event, and dialer configuration
information.
Panel operation report: Displays firmware version, marketplace, language, AC fail
delay, reset inhibit, zone re-sound, auto signal silence, in suite silence time, key #1,
key #2, aux power reset, lock remote read, AC voltage, date format, daylight savings,
minutes offset, day start, night start, mapping, LCD banner, IP (IP address), MSK
(subnet mask), and GWY (gateway), and event notification type configuration
information.
Panel configuration report: Displays dialer, network, printer, annunciator class,
annunciator, and NAC configuration information.
Devices report: Displays function, type, zone, label, follow, day sensitivity, night
sensitivity, day prealarm percent, night prealarm percent, correlation groups, and
event notification configuration information.