Appendix C: Front panel menu flowcharts
234 Vigilant VS1 and VS2 Technical Reference Manual
Advanced Program: Loop Configuration — Device
menu
Device
Loop 01<>
Device
Zone 01<>
Label >
Event Notification
Correlation Groups
Day Sens Normal<>
Night Sens Normal<>
Day PreAlarm% 50<>
Night PreAlarm% 50<>
Base Type Standard<>
Follow Alarm<>
Latched Yes/No<>
Type Smoke<>
Save
Device
Number XXX
Loop XX Device XXX
Serial#
Event Notification
Active
Trouble
Disable
PreAlarm
Alarm Verify
Maint Alert
Test
Label
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
<-Save <-Back
Notification
Printer Yes<>
CODER 10-10-10-10
Dialer Account1&2<>
NET Yes<>
CID 110
Save
Correlation Groups
Group XXX
Status Included
<-Enter <-Exit
Loop Configuration
Correlation Groups
Device

Table of Contents