Chapter 2: Front panel programming
Vigilant VS1 and VS2 Technical Reference Manual 65
Alarm: The base activates its relay when the detector goes into alarm. The base will
not restore until the alarm event has been restored.
Alarm and verify (ALM+VFY): The base activates its relay when the detector goes into
alarm verify and continues when the detector goes into alarm. The base will not
restore until both events have been restored.
Alarm and prealarm (ALM+PALM): The base activates its relay when the detector
goes into prealarm and continues when the detector goes into an alarm. The base
will not restore until both events have been restored.
Riser: The base is triggered individually by the loop controller (sounder bases only)
None: A correlation group triggers the base. It can be applied to both relay and
sounder bases and is used for relay bases configured as latched output devices.
Note: All base follow settings except “Head” and “Riser” can be activated by
correlation groups.
Incremental programming procedure
Referring to Table 20 on page 64, follow these steps to auto program the panel. Not
all options shown in Table 20 are displayed on all systems.
Notes
• Use the Right or Left Arrow button rather than the Enter button to select values
for each option. The Enter button starts the incremental program sequence
immediately no matter which option the cursor is on.
• The values you select are preserved and will be displayed as defaults the next
time you incrementally program the panel.
To perform incremental programming:
1. Press the menu button and choose Program.
2. Choose Incremental Program.
3. Enter a level two password.
4. Set the incremental programming options using
Table 20 on page 64.
5. When you have finished, press Enter.
The panel begins incremental programming and
displays the number of devices on the system. If the
panel has two loops, the device counts for each loop
are given separately. The system displays the
number of old and new devices.
6. Press Enter to continue.
Main Menu
Reports
Test
Control
Program
⇩
Program
Incremental Program
Auto Program
Advanced Program
⇩
Enter Password
0000
⇩
Incremental Program
Loop Loop 1>
Label Devices No>
Label Zones No>
⇩